Languages :

Mgm Types

Home » Mining Cables » MGM 112 TYPE E2, TYPE E4, TYPE E5

MGM 112 TYPE E2, TYPE E4, TYPE E5

APPLICATION

Used for supplying excavating, crushing machines and equipment.

Certificates
Technical Information

CONDUCTOR : Electrolytic, stranded, tinned copper wire IEC 60228 Class 5
INSULATION : EPR
LAYUP : Cores are laid up over a cradle without contacting each other (except for Tip E2).
BEDDING : Rubber based bedding compound.
ARMOUR : Galvanized steel pliable armour.
OUTER SHEATH : Heavy duty chloroprene outer sheath.

RELATED STANDARDS : MGM 112/1984
RATED VOLTAGE : 660/1100 V
TEST VOLTAGE : 3 kV

Cross Section 2×4 4×2,5 4×4 4×6 4×10 4×16 4×25 4×35 4×50 4×70
MGM 112 TYPE E2 E4
Conductors
Conductor diameter Nom. mm 2.60 2.10 2.70 3.30 4.40 5.50 7.10 8.40 10.10 11.90
Insulation thickness mm 1.0 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.7
Cable details
Radial thickness of inner sheath mm 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 3.8
Size of armour mm 7/0,45 7/0,45 7/0,45 7/0,70 7/0,70 7/0,70 7/0,70 7/0,90 7/0,90 7/0,90
Radial thickness of outer sheath mm 2.5 2.5 2.5 3.8 3.8 3.8 4.3 4.7 5.1 5.7
Min. overall diameter mm 23.9 26.2 27.7 36.7 38.8 41.5 46.1 51.0 56.1 64.8
Max. overall diameter mm 26.4 28.6 30.1 38.8 41.0 44.0 49.8 56.1 61.8 71.4
Min. bending radius mm 264 286 301 388 410 440 498 561 618 714
Appx. cable weight kg/km 950 1.28 1.45 2.45 2.9 3.6 4.45 5.65 7.35 9.5
Copper weight kg/km 80 100 160 240 390 620 960 1.35 1.92 2.69
Electrical details
“Continuous current
rating at 25°C Ambient”
A 28 28 37 46 63 85 110 135 170 205
Max. DC resistance at 20°C
Phase Conductor Ω /km 5.09 8.21 5.09 3.39 1.95 1.24 0.795 0.565 0.393 0.277
Nominal Kesit 4×95 4×120 4×150 5×4 5×6 5×10 5×16
TYPE E4 E5
Conductors
Number and cross section mm2 4×95 4×120 4×150 5×4 5×6 5×10 5×16
Stranding mm 475/0,50 608/0,50 756/0,50 56/0,30 84/0,30 80/0,40 126/0,40
Conductor diameter Nom. mm 13.90 15.80 17.00 2.60 3.30 4.40 5.50
Insulation thickness mm 2.0 2.2 2.3 1.4 1.5 1.5 1.5
Cable details
Radial thickness of inner sheath mm 3.8 5.0 5.0 2.0 2.0 2.5 2.5
Size of armour mm 7/0,90 7/1,25 7/1,25 7/0,45 7/0,50 7/0,70 7/0,70
Radial thickness of outer sheath mm 6.3 3.8 7.3 2.5 3.8 3.8 3.8
Min. overall diameter mm 74.9 83.8 91.4 31.0 38.0 42.4 46.5
Max. overall diameter mm 78.6 89.0 95.3 32.3 40.0 45.0 48.9
Min. bending radius mm 786 890 953 323 400 450 489
Appx. cable weight kg/km 10.95 15.6 18.5 1.75 2.9 3.9 4.8
Copper weight kg/km 3.65 4.61 5.76 200 290 480 770
Electrical details
“Continuous current
rating at 25°C Ambient”
A 250 295 320 28 46 63 85
Max. DC resistance at 20°C
Phase Conductor Ω /km 0.210 0.164 0.132 5.09 3.39 1.95 1.24

 