Languages :

Mgm Types

Home » Mining Cables » MGM 109 TYPE 3023

MGM 109 TYPE 3023

APPLICATION

Used as fixed installation cable for supplying machines and equipment.

Certificates
Technical Information

CONDUCTOR : Electrolytic, stranded, copper wire IEC 60228 Class 2
INSULATION : PVC
LAYUP : All cores are laid up in contact with each other.
BEDDING : PVC based bedding compound.
ARMOUR : Two layers of galvanized steel pilable armour.
SEPERATOR : Galvanized steel tape (optional).
OUTER SHEATH : Speacial PVC compound

RELATED STANDARDS : MGM 109/1983
RATED VOLTAGE : 1900/3300 V
TEST VOLTAGE : 10 kV

Cross Section 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185 3×240 3×300 3×400
Phase and Earth Conductors
Number and cross section mm2 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185 3×240 3×300 3×400
Radial thickness of inner sheath mm 1.6 1.6 1.6 1.8 1.8 1.8 2.2 2.2 2.2 2.6 2.6 2.6
Inner sheath diameter mm 22.8 25.4 27.6 31.2 34.6 38.5 42.5 46.6 50.5 56.6 62.4 70.4
Size of armour mm 1/1,6 1/1,6 1/1,6 1/2,0 1/2,0 1/2,0 1/2,5 1/2,5 1/2,5 1/2,5 1/2,5 1/2,5
Radial thickness of outer sheath mm 2.0 2.0 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.9 3.1 3.3
Min. overall diameter mm 31.9 34.5 36.9 42.3 45.9 50.0 56.4 60.7 64.8 71.1 77.3 85.7
Max. overall diameter mm 35.9 38.5 40.9 46.3 49.9 54.0 60.4 64.7 68.8 75.1 81.3 89.7
Min. bending radius mm 359 385 409 463 499 540 604 647 688 751 813 897
Appx. cable weight kg/km 2.5 3 3.5 4.6 5.55 6.8 8.55 9.8 11.35 13.95 16.7 20.75
Copper weight kg/km 465 700 1.01 1.48 2.17 3.07 3.79 4.88 6.12 8.08 10.29 13.75
Electrical details
“Continuous current
rating at 25°C Ambient”
A 82 108 135 168 207 250 292 335 382 453 523 620
Max. DC resistance at 20°C
Phase and earth conductors Ω /km 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
Armour Ω /km 1.53 0.97 0.699 0.516 0.357 0.257 0.204 0.165 0.132 0.101 0.0801 0.0627

 

We use cookies on our website to provide you a better experience. For detailed information please visit Our Cookie Policy and Clarification Text.