Languages :

Mgm Types

Home » Mining Cables » MGM 118 TYPE 6110

MGM 118 TYPE 6110

APPLICATION

Used as fixed installation cable tor supplying machines and equipment.

Certificates
Technical Information

CONDUCTOR : Electrolytic, stranded, copper wire IEC 60228 Class 1 or 2
INSULATION :PVC
SEPERATOR : Semiconductor layer
SCREEN: Cores are individually screened with copper backed tape
LAYUP : All cores are laid up in contact with each other.
BEDDING : PVC based bedding compound.
ARMOUR : Galvanized steel pilable armour.
SEPERATOR : Galvanized steel tape (optional).
OUTER SHEATH : Speacial PVC compound.

RELATED STANDARDS : MGM 109/1983
RATED VOLTAGE : 3800/6600 V
TTEST VOLTAGE : 10 kV

Cross Section 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185
Phase and Earth Conductors
Number and cross section mm2 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185
Cable details
Radial thickness of inner sheath mm 1.4 1.8 1.8 1.8 1.8 2.2 2.2 2.2 2.6
lnner sheath diameter mm 31.0 35.0 37.5 38.9 41.7 45.7 49.6 53.7 57.9
Size of armour mm 1/1,6 1/2,0 1/2,0 1/2,0 1/2,0 1/2,5 1/2,5 1/2,5 1/2,5
Radial thickness of outer sheath mm 2.0 2.1 2.2 2.2 2.3 2.5 2.6 2.6 2.8
Min. overall diameter mm 35.0 39.5 43.0 44.0 47.5 53.5 57.0 61.0 67.5
Max. overall diameter mm 39.0 43.5 47.0 48.0 51.5 57.5 61.0 65.0 71.5
Min. bending radius mm 390 435 470 480 515 575 610 650 715
Appx. cable weight kg,lkm 2,950 3,860 4,450 5,450 6,850 8,900 10,380 12,150 14,700
Copper weight kg,lkm 631 900 1,208 1,750 2,466 3,336 4,226 5,270 6,498
Electrical details
“Continuous current rating at 25°c Ambient” A 94 125 150 175 220 265 305 345 390
Max. DC resistance at 20°C
Phase and earth conductors Ω/km 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991
Armour Ω/km 1.92 1.21 0.873 0.645 0.447 0.322 0.255 0.207 0.165

 

We use cookies on our website to provide you a better experience. For detailed information please visit Our Cookie Policy and Clarification Text.