APPLICATION

Used as fixed installation cable for supplying machines and equipment.

Certificates
Technical Information

CONDUCTOR : Electrolytic, stranded, copper wire IEC 60228 Class 1 or 2
INSULATION : PVC
SEPERATOR : Semiconductor layer
LAYUP : Al/ cores are laid up in contact with each other.
BEDDING : PVC based bedding compound.
ARMOUR : Two layers of galvanized steel pilable armour.
SEPERATOR : Galvanized stee/ tape (optional).
OUTER SHEATH : Speacial PVC compound.

RELA TED STANDARDS : MGM 109/1983
RATED VOLTAGE : 3800/6600 V
TEST VOLTAGE : 17 kV

Cross Section 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185
Phase and Earth Conductors
Number and cross section mm2 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185
Cable details
Radial thickness of inner sheath mm 1.4 1.8 1.8 1.8 1.8 2.2 2.2 2.2 2.6
lnner sheath diameter mm 30.0 34.0 36.5 37.9 40.7 44.7 48.6 52.7 56.9
Size of armour mm 1/1,6 1/2,0 1/2,0 1/2,0 1/2,0 1/2,5 1/2,5 1/2,5 1/2,5
Radial thickness of outer sheath mm 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9
Min. overall diameter mm 38.7 43.9 46.2 49.2 52.9 59.7 63.2 67.4 72.3
Max. overall diameter mm 42.7 47.9 50.2 53.2 56.9 63.7 67.2 71.4 76.3
Min. bending radius mm 427 479 502 532 569 637 672 714 763
Appx. cable weight kg/km 4,450 5,850 6,500 7,400 8,550 11,250 12,550 14,200 16,300
Copper weight kg/km 461 720 1,008 1,440 2,086 2,836 3,706 4,820 6,078
Electrical details
“Continuous current rating at 25°c Ambient” A 86 110 135 160 200 245 285 325 370
Max. DC resistance at 20°C
Phase and earth conductors Ω/km 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991
Armour Ω/km 1.53 0.969 0.699 0.516 0.357 0.257 0.204 0.165 0.132

 