Languages :

Mgm Types

Home » Mining Cables » MGM 118 TYPE 6010

MGM 118 TYPE 6010

APPLICATION

Used as fixed installation cable for supplying machines and equipment.

Certificates
Technical Information

CONDUCTOR : Electrolytic, stranded, copper wire IEC 60228 Class 1 or 2
INSULATION : PVC
SEPERATOR : Semiconductor /ayer
LAYUP : Al/ cores are /aid up in contact with each other.
BEDDING : PVC based bedding compound.
ARMOUR : Two layers of galvanized steel pilable armour.
SEPERATOR : Galvanized stee/ tape (optional).
OUTER SHEATH : Speacial PVC compound.

RELATED STANDARDS : MGM 109/1983
RATED VOLTAGE : 3800/6600 V
TEST VOLTAGE : 17 kV

Cross Section 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185
Phase and Earth Conductors
Number and cross section mm² 3×16 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185
Cable details
Radial thickness of inner sheath mm 1.4 1.8 1.8 1.8 1.8 2.2 2.2 2.2 2.6
lnner sheath diameter mm 30.0 34.0 36.5 37.9 40.7 44.7 48.6 52.7 56.9
Size of armour mm 1/1,6 1/2,0 1/2,0 1/2,0 1/2,0 1/2,5 1/2,5 1/2,5 1/2,5
Radial thickness of outer sheath mm 2.0 2.1 2.2 2.2 2.3 2.5 2.6 2.6 2.8
Min. overall diameter mm 33.9 38.3 40.6 43.4 47.1 53.1 56.6 60.6 67.3
Max. overall diameter mm 37.9 42.3 44.6 47.4 51.1 57.1 60.6 64.6 71.3
Min. bending radius mm 379 423 446 474 511 571 606 646 713
Appx. cable weight kg/km 2,700 3,600 4,200 5,100 6,450 8,450 9,900 11,600 14,550
Copper weight kg/km 461 720 1,043 1,540 2,236 3,086 3,956 4,970 6,208
Electrical details
“Continuous current rating at 25°c Ambient” A 86 110 135 160 200 245 285 325 370
Max. DC resistance at 20°c
Phase and earth conductors Ω/km 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991
Armour Ω/km 1.92 1.21 0.873 0.645 0.447 0.322 0.255 0.207 0.165

 

We use cookies on our website to provide you a better experience. For detailed information please visit Our Cookie Policy and Clarification Text.