Languages :

Instrumentation Cables

Home » Instrumentation Cables » RE-Y(St)YSWAY-fl TIMF

RE-Y(St)YSWAY-fl TIMF

Application
These cables used for connecting instruments and control systems for analogue or digital signal transmission for indoor and outdoor applications.These cables shall not be connected directly to mains electricity supply or other low impedance sources, since they are not designed to be used for power supply.

Available Features on Request

• 300 V version

• Yw 105ºC version

• Hydrocarbon resistant

• Yv type reinforced sheath

• Oil resistant

• Anti termit / anti rodent

• UV resistant

• LSF (Low Smoke) version

Certificates
Technical Information

CONDUCTOR :Electrolytic, stranded, annealed plain copper wires to IEC 60228 Class 2 (Class 1 or Class 5 and / or tinned on request)
INSULAION :PVC compound to EN50290-2-21 Black / White / Red twisted triads with numbered cores
BINDER TAPE :Polyester foil on each twisted triad
INDIVIDUAL SCREEN :Aluminum/polyester foil with a tinned copper drain wire in direct contact with the metallic side of the foil
BINDER TAPE :Polyester foil on overall cable core formed by stranded pairs
COLLECTIVE SCREEN :Aluminum/polyester foil with a tinned copper drain wire in direct contact with the metallic side of the foil
INNER SHEATH :PVC compound to EN50290-2-22
ARMOUR :Round galvanised steel wires to EN 10257-1
OUTER SHEATH :Flame retardant PVC compound to EN50290-2-22 Blue for intrinsically safe cable Black for UV resistant and/or non-instrinsically safe cable Other colours on request

RATED VOLTAGE :500 V a.c.
AC TEST VOLTAGE :2000 V x 1 min. (core:core / core: screen)
WORKING TEMPERATURE : -30°C / + 70°C (during operation) – 5 °C / + 50°C (during installation)
MIN BENDING RADIUS (FIXED) :10 x D
CONSTRUCTION :EN 50288-7
MATERIAL TYPES & TESTS :EN 50290-2 series
ELECTRICAL & MECHANICAL TESTS :EN 50289 series
FLAME RETARDANT :IEC 60332 / 1-2, IEC 60332 / 3-24 Cat C

Conductor size (Class 2) nom. mm2 0.5 0.75 1 1.3 1.5 2.5
Conductor resistance max. Ω/km 36.7 25 18.5 14.2 12.3 7.6
Insulation resistance min. MΩxkm 100
L/R ratio max. µH/Ω 25 25 25 40 40 60
(*) At 20 °C
Cross Sections (mm2) Nominal Overall Diameter (mm) Approximate Weight (kg/km)
2x3x0,5 15.6 410
4x3x0,5 17.6 530
8x3x0,5 22.8 824
10x3x0,5 25.4 1080
12x3x0,5 26 1160
16x3x0,5 28.3 1374
20x3x0,5 31.2 1610
24x3x0,5 35.3 2092
2x3x0,75 16.7 465
4x3x0,75 19 613
5x3x0,75 21 810
6x3x0,75 22.6 910
8x3x0,75 24.8 1070
10x3x0,75 27.6 1260
12x3x0,75 28.4 1374
16x3x0,75 31.2 1650
20x3x0,75 35.5 2175
24x3x0,75 38.9 2506
2x3x1 17.1 488
4x3x1 19.4 655
5x3x1 21.7 870
6x3x1 23.2 968
8x3x1 25.6 1155
10x3x1 28.4 1360
12x3x1 29.4 1500
16x3x1 33 1990
20x3x1 36.7 2375
24x3x1 40.2 2736
2x3x1,3 18.1 540
4x3x1,3 21 842
5x3x1,3 22.7 960
6x3x1,3 24.3 1080
8x3x1,3 26.9 1295
10x3x1,3 30.1 1538
12x3x1,3 31 1686
16x3x1,3 35.1 2294
20x3x1,3 38.7 2698
24x3x1,3 42.5 3110
2x3x1,5 18.6 568
4x3x1,5 21.9 904
5x3x1,5 23.5 1020
6x3x1,5 25.4 1160
8x3x1,5 27.9 1383
10x3x1,5 31.2 1640
12x3x1,5 33 2004
16x3x1,5 36.7 2456
20x3x1,5 40.4 2890
24x3x1,5 45.2 3645
2x3x2,5 22 842
4x3x2,5 25.1 1150
5x3x2,5 27 1323
6x3x2,5 29.2 1502
8x3x2,5 33.2 2015
10x3x2,5 37.6 2448
12x3x2,5 38.7 2695
16x3x2,5 43.4 3560
20x3x2,5 48.5 4268
24x3x2,5 53.3 4948
We use cookies on our website to provide you a better experience. For detailed information please visit Our Cookie Policy and Clarification Text.