Languages :

Instrumentation Cables

Home » Instrumentation Cables » RE-2X(St)H-PIMF..CI

RE-2X(St)H-PIMF..CI

Application
These cables used for connecting instruments and control systems for analogue or digital signal transmissionfor indoor applications.These cables shall not be connected directly to mains electricity supply or other lowimpedance sources, since they are not designed to be used for power supply.Recommended for use where circuit integrity is required in case of fire.

Available Features on Request

• 300 V version

• Hv type reinforced sheath

• Hydrocarbon resistant

• Anti termit / anti rodent

• Oil resistant

• UV resistant

Certificates
Technical Information

CONDUCTOR :Electrolytic, stranded, annealed plain copper wires to IEC 60228Class 2 (Class 1 or Class 5 and / or tinned on request)
INSULATION :Mica tape + XLPE compound to EN50290-2-29Black / White twisted pairs with numbered cores
BINDER TAPE : Polyester foil on each twisted pair
INDIVIDUAL SCREEN :Aluminum/polyester foil with a tinned copper drain wire in direct contact with the metallic side of the foil
BINDER TAPE :Polyester foil on overall cable core formed by stranded pairs
COLLECTIVE SCREEN :Aluminum/polyester foil with a tinned copper drain wire in direct contact with the metallic side of the foil
OUTER SHEATH :Halogen free flame retardant LSZH compound to EN50290-2-27 Orange or Red for circuit integrity Blue for intrinsically safe cable Black for UV resistant and/or non-instrinsically safe cable

RATED VOLTAGE : 500 V a.c.
AC TEST VOLTAGE : 2000 V x 1 min. (core:core / core: screen)
WORKING TEMPERATURE : -40°C / + 90°C (during operation) – 5 °C / + 50°C (during installation)
MIN BENDING RADIUS (FIXED) : 7,5 x D
CONSTRUCTION : EN 50288-7
MATERIAL TYPES & TESTS : EN 50290-2 series
ELECTRICAL & MECHANICAL TESTS : EN 50289 series
FLAME RETARDANT : IEC 60332 / 1-2, IEC 60332 / 3-24 Cat C
FIRE RESISTANCE : IEC 60331 / 21, IEC 60331 / 1-2
HALOGEN CONTENT : IEC 60754 / 1-2
SMOKE EMISSION : IEC 61034 / 1-2

Conductor size (Class 2) nom. mm2 0.5 0.75 1 1.3 1.5 2.5
Conductor resistance max. Ω/km 36.7 25 18.5 14.2 12.3 7.6
Insulation resistance min. MΩxkm 5000
L/R ratio max. µH/Ω 25 25 25 40 40 60
(*) At 20 °C
Cross Sections (mm2) Nominal Overall Diameter (mm) Approximate Weight (kg/km)
2x2x0,5 11.9 118
4x2x0,5 14.1 186
8x2x0,5 19.3 334
10x2x0,5 22.1 414
12x2x0,5 22.9 470
16x2x0,5 25.6 600
20x2x0,5 29 755
24x2x0,5 32.3 896
2x2x0,75 12.9 140
4x2x0,75 15.2 220
5x2x0,75 16.6 260
6x2x0,75 18.3 310
8x2x0,75 20.8 400
10x2x0,75 23.8 493
12x2x0,75 24.6 560
16x2x0,75 27.5 717
20x2x0,75 30.9 882
24x2x0,75 34.7 1070
2x2x1 13.2 150
4x2x1 15.6 243
5x2x1 17.1 288
6x2x1 18.9 343
8x2x1 21.4 440
10x2x1 24.5 545
12x2x1 25.4 622
16x2x1 28.4 798
20x2x1 32.1 998
24x2x1 35.8 1190
2x2x1,3 14.2 172
4x2x1,3 16.8 280
5x2x1,3 18.6 342
6x2x1,3 20.3 397
8x2x1,3 23 510
10x2x1,3 26.6 646
12x2x1,3 27.5 738
16x2x1,3 30.8 948
20x2x1,3 34.8 1184
24x2x1,3 38.8 1410
2x2x1,5 14.3 180
4x2x1,5 17 296
5x2x1,5 18.8 362
6x2x1,5 20.7 430
8x2x1,5 23.5 554
10x2x1,5 26.9 687
12x2x1,5 27.9 787
16x2x1,5 31.4 1030
20x2x1,5 35.2 1265
24x2x1,5 39.5 1525
2x2x2,5 17.1 250
4x2x2,5 20.3 418
5x2x2,5 22.5 510
6x2x2,5 24.8 608
8x2x2,5 28.2 784
10x2x2,5 32.5 987
12x2x2,5 33.6 1134
16x2x2,5 37.8 1480
20x2x2,5 42.7 1843
24x2x2,5 47.9 2220
We use cookies on our website to provide you a better experience. For detailed information please visit Our Cookie Policy and Clarification Text.