APPLICATION
These cables use for control and monitoring circuits, interlocking circuits, indicating circuits and internal wiring of equipment run on trays exposed.
CONDUCTOR: Tinned annealed stranded copper wires acc. to EN 50306-2
FIRE BARRIER: Mica tape over the conductor
INSULATION: Low smoke, halogen free, heat resistant, cross linked compound
OUTER SHEATH: Halogen free, heat resistant, cross linked compound, Type EM 104 acc. to EN 50264-1
STANDARD: Based on EN 50306-4
GUIDE TO USE: EN 50355, EN 50343
GENERAL REQUIREMENTS: EN 50306-1, EN 50306-2
FLAME PROPAGATION SINGLE CORE: EN 60332-1-2
FLAME PROPAGATION BUNCHED CABLE: EN 60332-3-24
SMOKE DENSITY: EN 61034-2
HALOGEN FREE: EN 60754-1, EN 60754-2, EN 60684-2
CORROSIVITY OF GASES: EN 60754-2
MINERAL OIL, ACID, ALKALI RESISTANT: EN 60811-404
OZONE RESISTANT: EN 50305
NO FLUORINE: EN 60684-2
FIRE PROTECTION ON RAILWAY VEHICLES: EN 45545
CIRCUIT INTEGRITY: EN 50200
CONDUCTOR RESISTANCE: EN 50306-2
UV RESISTANT: BS EN 50289-4-17 Method B
RATED VOLTAGE: 300 V
TEST VOLTAGE: 2 kV
MAX. CONDUCTOR TEMPERATURE: 90°C
MIN. AMBIENT TEMPERATURE: -40°C
SHORT CIRCUIT TEMPERATURE: 160°C (Max. 5 s)
THERMAL ENDURANCE TEMP.: 110°C / 125°C (20 000 h)
MIN. BENDING RADIUS: EN 50355 Tab.16
FIXED D≤12 MM: 4xD mm
FIXED D>12 MM: 5xD mm
CAREFUL BENDING D≤12 MM: 3xD mm
CAREFUL BENDING D>12 MM: 4xD mm