APPLICATION

Used as fixed installation cables in various electromechanical and electronic equipments on shore.

Certificates
Technical Information

CONDUCTOR : Electrolytic, stranded, annealed copper wire. IEC 60228 Class 5 (tinned on request).
INSULATION : PVC or PUR compound.
BEDDING : Rubber or PVC compound.
OUTER SHEATH : PUR compound. Color: Yellow, Orange or Black.

CONSTRUCTION : IEC 60502 / 1
TESTS AND MATERIAL : IEC 60092 /350-353
WORKING TEMPERATURE : -35°C / + 90°C
MIN. BENDING RADIUS (FIXED) : 8 x (Overall Diameter)
RATED VOLTAGE : 0,6/1 kV
TEST VOLTAGE : 3,5kV

CROSS SECTION
(mm2)
OVERALL DIAMETER
(mm)
APPX. WEIGHT
(kg / km)
COPPER WEIGHT
(kg / km)
2×0.75 6.6 60 15
2×1 6.8 70 20
2×4 10.8 175 77
2×6 12.0 230 116
2×10 16.4 455 192
3×0.75 7.2 75 22
3×1 7.4 85 29
3×1.5 8.7 110 44
3×2.5 10.2 155 72
3×4 11.7 225 116
3×6 13.0 295 173
3×10 17.8 580 288
3×16 20.1 790 461
3×25 25.6 1280 720
3×35 28.4 1640 1008
3×50 33.3 2300 1440
3×70 38.0 3165 2016
3×95 42.8 4050 2736
4×0.75 8.1 95 29
4×1 8.5 105 39
4×1.5 9.9 145 58
4×2.5 11.4 205 96
4×4 13.0 285 154
4×6 14.4 375 231
4×10 19.5 725 384
4×16 23.0 1035 615
4×25 28.3 1600 960
4×35 31.8 2110 1344
4×50 37.0 2915 1920
4×70 39.5 3725 2688
4×95 47.5 5150 3648

 