Languages :

Marine Cables

Home » Marine Cables » M2X

M2X

Application

Fixed wiring in control panels, switch boadrs and various electrical enclosures and also used as fixed installation
cables in various electromechanical and electronic equipments.

* Minimum recommended installation temperature -15°C
For core identification, diameter tolerances and other details see technical information section

Certificates
Technical Information

CONDUCTOR: Electrolytic, stranded, annealed bare copper wire IEC 60228 Class 5 (Class 2 and / or tinned on request)
INSULATION: Halogen free, flame retardant, cross linked polyolefin compound (HF90).
COLOR: Black, red, blue and other colours

CONSTRUCTION: IEC 60092 / 353
TESTS AND MATERIAL: IEC 60092 / 350-360
FLAME RETARDANT: IEC 60332 / 1-2, IEC 60332 / 3-22 Cat A
HALOGEN CONTENT: IEC 60754 / 1-2
SMOKE EMISSION: IEC 61034 / 1-2 ( DIN EN 50268 / 1-2)
OZON RESISTANCE : IEC60811 / 403
TEMPERATURE RANGE : -40°C / + 90°C
MIN. BENDİNG RADIUS (FIXED) : 4 x D
RATED VOLTAGE: 0,6/1 kV
TEST VOLTAGE: 3,5 kV
UV AND SUNLIGHT RESISTANCE : EN 50289-4-17 A&B, ISO 4892-2&3

Cross Section (mm²) Nominal Overall Diameter (mm) Approximate Weight (kg / km) Bending Radius Fixed Min. (mm) Max Resistance of Conductors at 20°C
(ohm / km)
Current Carrying Capacity at 45°C (A)
1 x 1 2.7 15 11 19.5 16
1 x 1,5 2.9 19 12 13.3 21
1 x 6 4.2 59 17 3.3 50
1 x 10 5.5 98 22 1.91 71
1 x 16 6.2 148 25 1.21 93
1 x 25 8.6 240 35 0.78 122
1 x 35 9.7 330 39 0.554 152
1 x 50 11.6 464 47 0.386 195
1 x 70 13 648 53 0.272 240
1 x 95 14.9 841 60 0.206 286
1 x 120 17 1076 68 0.161 332
1 x 150 18.8 1336 76 0.129 382
1 x 185 21.5 1675 86 0.106 432
1 x 240 24 2172 96 0.0801 508
1 x 300 26.6 2703 107 0.0641 590

 

We use cookies on our website to provide you a better experience. For detailed information please visit Our Cookie Policy and Clarification Text.