Application
Used as fixed installation cables in various electromechanical and electronic equipments. Since it has type approval, it can be used in marine switchboards.
CONDUCTOR : Electrolytic, stranded, annealed copper wire IEC 60228 Class 5
(Class 2 and / or tinned on request)
INSULATİON : Halogen free, flame retardant, cross linked polyolefin
compound (HF90). Double insulation is available on request.
COLOR : Black, red, blue and other colours
CONSTRUCTION : IEC 60092 / 376
TESTS AND MATERIAL : IEC 60092 / 350-360
FLAME RETARDANT : IEC 60332 / 1-2, IEC 60332 / 3-22 Cat A
HALOGEN CONTENT : IEC 60754 / 1-2
SMOKE EMISSION : IEC 61034 / 1-2 ( DIN EN 50268 / 1-2)
OZON RESISTANCE : IEC60811 / 403
TEMPERATURE RANGE : -40°C / + 90°C
MIN. BENDING RADIUS (FIXED) : 4 x D
RATED VOLTAGE : 300 / 500 V
TEST VOLTAGE : 1,5 kV
UV AND SUNLIGHT RESISTANCE : EN 50289-4-17 A&B, ISO 4892-2&3
| Cross Section (mm²) | Nominal Overall Diameter (mm) | Approximate Weight (kg / km) | Bending Radius Fixed Min. (mm) | Max Resistance of Conductors at 20°C (ohm / km) | Current Carryng Capacity at 45°C (A) |
|---|---|---|---|---|---|
| 1 x 0,50 | 2.1 | 8 | 10 | 40.4 | 11 |
| 1 x 0,75 | 2.3 | 11 | 10 | 26 | 13 |
| 1 x 2,5 | 3.2 | 28 | 13 | 7.98 | 29 |