APPLICATION
These flexible low-voltage reeling cables are designed for power supply applications under high mechanical stresses. They are particularly suitable for use in cable reels, hoists, lifts, portable engines, traction motors, agricultural equipment, and monospiral reeling applications, where frequent winding and unwinding occur. Specifically engineered for operations involving simultaneous tensile strain, torsional stress, and forced cable guidance, they are ideal for demanding applications such as Electrified Rubber Tyred Gantry (ERTG) cranes. These cables can be used in dry and wet conditions, outdoors, and in oily areas. Additionally, the textile braiding is embedded between the inner and outer sheath, enhancing durability and performance.
CONDUCTOR: Electrolytic annealed, class 5 stranded bare copper wires
INSULATION: 3GI3 type cross-linked elastomeric compound (VDE 0207 – Part 20)
CORE ARRANGEMENT: Three-core design, with split earth conductor in the interstices, laid up with a left-hand lay. Special tape is applied over the core bundle.
INNER SHEATH: 5GM3 type special rubber compound (VDE 0207 – Part 21)
REINFORCEMENT: Antitorsion textile braided embeded sheath
OUTER SHEATH: 5GM5 type special rubber compound (VDE 0207 – Part 21)
CONSTRUCTION: Based on VDE 0250-814
GENERAL REQUIREMENTS: VDE 0250-1
GUIDE TO USE: VDE 0298-3, VDE 0298-4
ELECTRICAL TESTS: VDE 0472-501, 502, 503, 508
NON-ELECTRICAL TESTS: VDE 0472-401, 402, 602, 303, 615
CONDUCTOR RESISTANCE: VDE 0295, IEC 60228
FLAME RETARDANT: IEC 60332-1-2, VDE 0482-332-1-2
OIL RESISTANT: VDE 0473-811-404, EN 60811-404
RATED VOLTAGE: 600/1000 V (U0/U)
AC TEST VOLTAGE: 3,5 kV
OPERATING TEMPERATURE: -40°C to +90°C
MAX. CONDUCTOR OPERATING TEMP.: 90°C
CONDUCTOR SHORT-CIRCUIT: 250°C (Max. 5 sec)
MIN. INSTALLATION TEMP.: -15°C
MIN. BENDING RADIUS: VDE 0298-3
CURRENT CARRYING CAPACITIY: VDE 0298-4
MAX. TENSILE LOAD ON THE CONDUCTOR: 15 N/mm2
TORSIONAL STRESS: ± 50 °/m
TRAVEL SPEED: Permitted running speed up 240m/min
| CAN* | Cross-section (mm2) | Outer Sheath Diameter | Approx. Cable Weight (kg/km) | Min. Bending Radius Free moving (mm) | Current Carrying Capacity (**) (A) | Max. Electrical Resistance at 20°C (ohm/km) | ||
| Min. (mm) | Nom. (mm) | Max. (mm) | ||||||
| 4131.1 | 3×35 + 3×16/3 | 29,50 | 30,6 | 31,50 | 2.020 | 158 | 165 | 0,554 |
| 4131.2 | 3×50 + 3×25/3 | 35,00 | 36,4 | 37,00 | 2.878 | 185 | 205 | 0,386 |
| 4131.3 | 3×70 + 3×35/3 | 39,50 | 41,1 | 43,00 | 3.833 | 215 | 250 | 0,272 |
| 4131.4 | 3×95 + 3×50/3 | 43,50 | 45,3 | 46,00 | 4.838 | 230 | 300 | 0,206 |
| 4131.5 | 3×120 + 3×70/3 | 49,50 | 51,3 | 52,00 | 6.205 | 260 | 355 | 0,161 |
| 4131.6 | 3×150 + 3×70/3 | 53,00 | 54,9 | 56,00 | 7.283 | 280 | 405 | 0,129 |
| 4131.7 | 3×185 + 3×95/3 | 58,00 | 59,9 | 61,00 | 8.862 | 305 | 460 | 0,106 |
| 4131.8 | 3×240 + 3×120/3 | 66,50 | 68,7 | 70,00 | 11.577 | 350 | 540 | 0,0801 |
| 4131.9 | 3×300 + 3×150/3 | 72,00 | 74,7 | 76,00 | 14.152 | 380 | 620 | 0,0641 |
| 4131.10 | 3×400 + 3×240/3 | 83,50 | 86,2 | 88,00 | 18.393 | 440 | 720 | 0,0486 |
** Conductor temperature at 90 °C, Ambient air temperature at 30 °C
* CAN : Cable Article Numb