052XZ1-F

Certificates :

APPLICATIONS

These cables are used as power cable in hotels, hospitals, shoping centers, power plants, industrial plants, electrical circuits in crowded places and in places where higher safety required in case of fire. They can be used on and under plaster and available to use in dry, damp and wer places.

CONDUCTOR: Electrolytic annealed, class 5 stranded plain copper wires (tinned conductor on request)
INSULATION: XLPE compound (Cross-linked polyethylene), 2XI1 type (TS 13751)
FILLER: Halogen-Free compound
SHEATH: Halogen-Free compound, HM2 type (TS 13751 )
COLOR: Grey

RATED VOLTAGE: 300/500 V (U0/U)
AC TEST VOLTAGE: 2 kV
OPERATING TEMPERATURE: -30°C to +90°C
CONDUCTOR SHORT-CIRCUIT TEMP.: 250°C (Max. 5 sec)
MIN. INSTALLATION TEMP.: -5°C
MIN. BENDING RADIUS: Based on VDE 0298-3
CURRENT CARRYING CAPACITIES: IEC 60364-5-52 Tab B52.1 & B52.3 & B52.5 & B52.12

Cross Section (mm²)Nominal Overall Diameter (mm)Approximate Weight
(kg / km)
Min.Bending Radius
(free movement) (mm)
-Max. Resistance of Conductors
at 20°C (ohm / km)
2×0,75 7,80 84 31 26,00 
2×1 8,20 92 33 19,50 
2×1,5 8,40 105 34 13,30 
2×2,5 9,20 138 37 7,98 
2×4 10,60 187 42 4,95 
2×6 11,40 240 46 3,30 
2×10 14,20 386 57 1,91 
3×0,75 8,20 95 33 26,00 
3×1 8,60 104 34 19,50 
3×1,5 8,80 121 35 13,30 
3×2,5 9,60 158 38 7,98 
3×4 11,20 227 45 4,95 
3×6 12,40 301 50 3,30 
3×10 15,00 468 60 1,91 
4×0,75 8,70 109 35 26,00 
4×1 9,20 125 37 19,50 
4×1,5 9,50 144 38 13,30 
4×2,5 10,30 189 41 7,98 
4×4 12,50 297 50 4,95 
4×6 13,90 388 56 3,30 
4×10 16,30 584 65 1,91 
5×0,75 9,30 126 37 26,00 
5×1 9,90 143 40 19,50 
5×1,5 10,20 169 41 13,30 
5×2,5 11,10 224 44 7,98 
5×4 13,80 352 55 4,95 
5×6 15,10 458 60 3,30 
5×10 17,80 700 71 1,91