H05RN-F

H05RN-F Industrial Cable

Sertifikalar :

KULLANIM ALANI

These cables are avilable to use in both low and medium stressed subjects; as connection of fixed and mobile equipment connections such as household and office equipments. They can be used indoor, outdoor, damp places, oily, dry and wet environments.

CONDUCTOR: Electrolytic annealed, class 5 stranded plain copper wires (tinned conductor on request)
SEPERATOR: A suitable tape may be applied over the conductor
INSULATION: EI4 type cross-linked elastomeric compound, EPR (EN 50363-1)
SHEATH: EM2 type cross-linked elastomeric compound (EN 50363-2-1)
COLOR: Black

RATED VOLTAGE: 300/500 V (U0/U)
AC TEST VOLTAGE: 2 kV
OPERATING TEMPETATURE
IN FLEXING USE: -25°C to +60°C
IN FIXED USE: -40°C to +90°C
CONDUCTOR SHORT-CIRCUIT TEMP.: 200°C (Max. 5 sec)
MIN. INSTALLATION TEMP.: -25°C
MIN. BENDING RADIUS: EN 50565-1 Tab. 3
CURRENT CARRYING CAPACITIES: VDE 0298-4 Tab. 11

Cross Section (mm²)Nominal Overall Diameter (mm)Approximate Weight
(kg / km)
Min.Bending Radius
(free movement) (mm)
Max. Resistance of Conductors
at 20°C (ohm / km)
2×0,75 6,20 53 25 26,00 
2×1 6,80 66 27 19,50 
3×0,75 6,80 67 27 26,00 
3×1 7,20 79 29 19,50 
4×0,75 7,40 80 30 26,00 
4×1 7,85 94 31 19,50 