We use cookies on our website to provide you a better experience. For detailed information please visit our Cookie Policy and Clarification Text.
APPLICATION
Used as fixed installation cable for supplying machines and equipment.
CONDUCTOR : Electrolytic, stranded, copper wire IEC 60228 Class 1 or 2
INSULATION : PVC
SEPERATOR : Semiconductor Jayer
SCREEN : Cores are individualJy screened with copper backed tape
LAYUP : All cores are Jaid up in contact with each other.
BEDDING : PVC based bedding compound.
ARMOUR : Two layers of galvanized steel pilable armour.
SEPERATOR : Galvanized steel tape (optional).
OUTER SHEATH : Speacial PVC compound.
RELATED STANDARDS : MGM 109/1983
RATED VOLTAGE : 3800/6600 V
TEST VOLTAGE : 10 kV
Cross Section | 3×16 | 3×25 | 3×35 | 3×50 | 3×70 | 3×95 | 3×120 | 3×150 | 3×185 | |
---|---|---|---|---|---|---|---|---|---|---|
Phase and Earth Conductors | ||||||||||
Number and cross section | mm2 | 3×16 | 3×25 | 3×35 | 3×50 | 3×70 | 3×95 | 3×120 | 3×150 | 3×185 |
Conductor diameter | Nom.mm | 4.90 | 6.10 | 7.10 | 8.40 | 10.00 | 11.80 | 13.30 | 15.20 | 17.00 |
lnsulation thickness | mm | 3.4 | 3.4 | 3.4 | 3.4 | 3.4 | 3.4 | 3.4 | 3.4 | 3.4 |
Cable details | ||||||||||
Radial thickness of inner sheath | mm | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 2.2 | 2.2 | 2.2 | 2.6 |
lnner sheath diameter | mm | 30.0 | 34.0 | 36.5 | 37.9 | 40.7 | 44.7 | 48.6 | 52.7 | 56.9 |
Size of armour | mm | 1/1,6 | 1/2,0 | 1/2,0 | 1/2,0 | 1/2,0 | 1/2,5 | 1/2,5 | 1/2,5 | 1/2,5 |
Radial thickness of outer sheath | mm | 2.1 | 2.2 | 2.3 | 2.4 | 2.5 | 2.6 | 2.7 | 2.8 | 2.9 |
Min. overall diameter | mm | 40.5 | 45.6 | 48.5 | 51.0 | 54.5 | 61.5 | 65.0 | 69.0 | 74.0 |
Max. overall diameter | mm | 44.5 | 49.6 | 52.5 | 55.0 | 58.5 | 65.5 | 69.0 | 73.0 | 78.0 |
Min. bending radius | mm | 445 | 496 | 525 | 550 | 585 | 655 | 690 | 730 | 780 |
Appx. cable weight | kg/km | 4,850 | 6,250 | 6,950 | 7,850 | 9,050 | 11,850 | 13,200 | 14,850 | 17,050 |
Copper weight | kg/km | 631 | 900 | 1,208 | 1,650 | 2,316 | 3,086 | 3,976 | 5,070 | 6,368 |
Electrical details | ||||||||||
“Continuous current rating at 25°c Ambient” | A | 94 | 125 | 150 | 175 | 220 | 265 | 305 | 345 | 390 |
Max. DC resistance at 20°C | ||||||||||
Phase and earth conductors | Ω/km | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 | 0.0991 |
Armour | Ω/km | 1.53 | 0.969 | 0.699 | 0.516 | 0.357 | 0.257 | 0.204 | 0.165 | 0.132 |
Copyright © 2024 ÜNTEL KABLOLARI. All rights reserved.