Home » MGM Types » MGM 112 TYPE 62, TYPE 63, TYPE 64

MGM 112 TYPE 62, TYPE 63, TYPE 64

Mining Certficated Cables

Certificates :

APPLICATION

Used for supplying excavating, crushing machines
and equipment.

CONDUCTOR : Electrolytic, stranded, tinned copper wire IEC 60228 Class 5
INSULATION : EPR
SCREEN : Tinned copper / Nylon braided screen over cores.
LAYUP : All cores are laid up in contact with each other.
BEDDING : Rubber based bedding compound.
ARMOUR : Galvanized steel pliable armour.
OUTER SHEATH : Heavy duty chloroprene outer sheath.

RELATED STANDARDS : MGM 112/1984
RATED VOLTAGE : 660/1100 V
TEST VOLTAGE : 2,5 kV

Cross Section
2×43×44×4
MGM 112TYPE 62 TYPE 63TYPE 64
Conductors
Number and cross section
mm22×43×44×4
Strandingmm56/0,3056/0,3056/0,30
Conductor diameter
Nom. mm2.602.602.60
Insulation thickness
mm1.01.01.0
Cable details
Radial thickness of inner sheath
mm2.02.02.0
Min. inner sheath diameter
mm16.217.118.7
Max. inner sheath diameter
mm18.219.120.7
Size of armour
mm7/0,457/0,457/0,45
Radial thickness of outer sheath
mm2.52.52.5
Min. overall diameter
mm23.924.826.4
Max. overall diameter
mm26.427.328.9
Min. bending radius
mm270280290
Max. pulling tension
kgf487296
Appx. cable weight
kg/km1.081.231.4
Copper weight
kg/km132200264
Electrical details
“Continuous current
rating at 25°C Ambient”
A282828
Max. DC resistance at 20°C
Phase Conductor
Ω /km5.095.095.09
screens in parallel connection
Ω /km5.53.92.8
ArmourΩ /km4.914.634.16
Nom. reactance at 50Hz
Ω /km0.1190.1190.119
Nom. reactance at 60HzΩ /km0.1430.1430.143
Min. insulation resistance at 20°C
M Ω /km590590590
3 phase voltage drop on full load current
mV/A/m12,38*10.7210.72
We use cookies on our website to provide you a better experience. For detailed information please visit our Cookie Policy and Clarification Text.