Mining Certficated Cables

Certificates :

APPLICATION

Used as fixed installation cable for supplying machines
and equipment.

CONDUCTOR : Electrolytic, stranded, copper wire IEC 60228 Class 1 or 2
INSULATION : PVC
LAYUP : All cores are laid up in contact with each other.
BEDDING : PVC based bedding compound.
ARMOUR : Two layers of galvanized steel pilable armour.
SEPERATOR : Galvanized steel tape (optional).
OUTER SHEATH : Speacial PVC compound.

RELATED STANDARDS : MGM 109/1983
RATED VOLTAGE : 600/1000 V
TEST VOLTAGE : 3 kV

Cross Section
3×1,53×2,53×43×63×10
MGM 109 TYPE 1023
Phase and Earth Conductors
Number and cross section
mm23×1,53×2,53×43×63×10
Insulation thickness
mm0.80.80.80.81.0
Cable details
Radial thickness of inner sheath
mm0.80.80.80.80.8
Inner sheath diameter
mm7.410.312.413.616.5
Size of armour
mm1/0,91/0,91/0,91/1,251/1,25
Radial thickness of outer sheath
mm1.41.51.61.61.7
Min. overall diameter
mm9.716.318.621.426.5
Max. overall diameter
mm13.720.322.625.430.5
Min. bending radius
mm124203226254305
Appx. cable weight
kg/km3507509101.31.7
Copper weight
kg/km4575120190310
Electrical details
“Continuous current
rating at 25°C Ambient”
A1826344461
Max. DC resistance at 20°C
Phase and earth conductors
Ω /km12.17.414.613.081.83
ArmourΩ /km20.179.716.154.112.44
Cross Section
4×1,54×2,54×44×64×10
MGM 109 TYPE1024
Phase and Earth Conductors
Number and cross section
mm24×1,54×2,54×44×64×10
Insulation thickness
mm0.80.80.80.81.0
Cable details
Radial thickness of inner sheath
mm0.80.80.80.80.8
Inner sheath diameter
mm9.611.113.414.818.1
Size of armour
mm1/0,91/0,91/1,251/1,251/1,25
Radial thickness of outer sheath
mm1.51.51.61.71.8
Min. overall diameter
mm15.517.121.222.826.2
Max. overall diameter
mm19.521.125.226.830.2
Min. bending radius
mm195211252268302
Appx. cable weight
kg/km7508501.251.481.98
Copper weight
kg/km60100160240385
Electrical details
“Continuous current
rating at 25°C Ambient”
A1826344461
Max. DC resistance at 20°C
Phase and earth conductors
Ω /km12.17.414.613.081.83
ArmourΩ /km16.109.716.154.112.44