We use cookies on our website to provide you a better experience. For detailed information please visit our Cookie Policy and Clarification Text.
Search
CONDUCTOR : Strand of annealed tinned or bare copper wires According to IEC C 60228 – Class 2 AWG types to ASTM B8 – Class B or Class C
SEMICONDUCTIVE LAYER : Extruded Semiconductive material
INSULATION : EPR- Ethylene probylene rubber material
OUTER JACKET : CPE-XL-HD or CR – HD or NEoprene or other suitable jacketing material according to NEMA WC71 / IECA S-96-659.
CONDUCTOR OPERATING TEMPERATURE : -25ºC / +90ºC
RATED VOLTAGE : 5 kV
TEST VOLTAGE : 13 kV
BENDING RADIUS : 5 x Outer Diameter
STANDARD OF TEST : NEMA WC71 /ICEA S-96-659-2014 FAA Specification for L824-AC No. 150/5345-7F
| Construction (*) | Cross Section | Overall Diameter mm | Approx Weight kg/km | Max. Resistance of Conductors at 20 ºC (ohm/km) | Current Carrying Capacity at 45 ºC (A) |
|---|---|---|---|---|---|
| BCL2 / EXSC / EPR / CPE-XL | 1X6 mm² | 14,2 | 255 | 3,08 | 52 |
| TCL2 / EXSC / EPR / CPE-XL | 1X6 mm² | 14,2 | 255 | 3,11 | 52 |
| BAWGB / EXSC / EPR / CPE-XL | 1X8 AWG | 14,8 | 293 | 2,10 | 64 |
| TAWGB / EXSC / EPR / CPE-XL | 1X8 AWG | 14,8 | 293 | 2,18 | 64 |
| BAWGB / EXSC / EPR / CPE-XL | 1X6 AWG | 15,8 | 362 | 1,33 | 85 |
| TAWGB / EXSC / EPR / CPE-XL | 1X6 AWG | 15,8 | 362 | 1,38 | 85 |