CONDUCTOR : Stranded annealed tinned or bare copper wires According to IEC 60228 – Class 2 AWG types to ASTM B8 – Class B or Class C
SEMICONDUCTIVE LAYER : Extruded Semiconductive material
INSULATION : XLPE – Cross linked polyethylene material
SEMICONDUCTIVE LAYER : Semiconductive tape helically applied
SCREEN : Minimum 20% overlap and 100% coverage helically applied Copper Tape
OUTER JACKET : PVC or PE or HF (halogen free) or other suitable jacketing material according to NEMA WC74 / ICEA S-93-639.
CONDUCTOR OPERATING TEMPERATURE : -25ºC / +90ºC
RATED VOLTAGE : 5 kV
TEST VOLTAGE : 18 kV
BENDING RADIUS : 12 x Outer Diameter
STANDARD OF TEST : ICEA S-93-639 / NEMA WC74 FAA Specification for L 824 – AC No. 150 / 5345-7F
| Construction (*) | Cross Section | Overall Diameter mm | Approx Weight kg/km | Max. Resistance of Conductors at 20 ºC (ohm/km) | Current Carrying Capacity at 45 ºC (A) |
|---|---|---|---|---|---|
| BCL2 / EXSC / XLPE / SCT / CUT / PE | 1X6 mm² | 12,4 | 187 | 3,08 | 52 |
| BCL2 / EXSC / XLPE / SCT / CUT / PVC | 1X6 mm² | 12,4 | 213 | 3,08 | 52 |
| TCL2 / EXSC / XLPE / SCT / CUT / PE | 1X6 mm² | 12,4 | 187 | 3,11 | 52 |
| TCL2 / EXSC / XLPE / SCT / CUT / PVC | 1X6 mm² | 12,4 | 213 | 3,11 | 52 |
| BAWGB / EXSC / XLPE / SCT / CUT / PE | 1X8 AWG | 13,0 | 221 | 2,10 | 64 |
| BAWGB / EXSC / XLPE / SCT / CUT / PVC | 1X8 AWG | 13,0 | 248 | 2,10 | 64 |
| TAWGB / EXSC / XLPE / SCT / CUT / PE | 1X8 AWG | 13,0 | 221 | 2,18 | 64 |
| TAWGB / EXSC / XLPE / SCT / CUT / PVC | 1X8 AWG | 13,0 | 248 | 2,18 | 64 |
| BAWGB / EXSC / XLPE / SCT / CUT / PE | 1X6 AWG | 14,0 | 283 | 1,33 | 85 |
| BAWGB / EXSC / XLPE / SCT / CUT / PVC | 1X6 AWG | 14,0 | 312 | 1,33 | 85 |
| TAWGB / EXSC / XLPE / SCT / CUT / PE | 1X6 AWG | 14,0 | 283 | 1,38 | 85 |
| TAWGB / EXSC / XLPE / SCT / CUT / PVC | 1X6 AWG | 14,0 | 312 | 1,38 | 85 |