CONDUCTOR : Electrolytic, stranded, tinned copper wire IEC 60228 Class 5
INSULATION : EPR
SEPERATOR : Colored Textile tape for core identification.
SCREEN : Tinned copper / Nylon braided screen over phase cores. Pilot core and ground core are not screened.
LAYUP : All cores are laid up in contact with each other.
BEDDING : Rubber based bedding compound.
OUTER SHEATH : Heavy duty chloroprene outer sheath.
RELATED STANDARDS : BS 6708
RATED VOLTAGE : 125/72 V
TEST VOLTAGE : 1,5 kV
Cross Section | 5×6 | |
---|---|---|
Phase Conductor | ||
Number and cross section | mm2 | 3×6 |
Stranding | mm | 84/0,30 |
Conductor diameter | Nom. mm | 3.30 |
Insulation thickness | mm | 1.00 |
Total screen cross section | mm2 | 11 |
Earth Conductor | ||
Number and cross section | mm2 | 1×6 |
Stranding | mm | 84/0,30 |
Conductor diameter | Nom. mm | 3.30 |
Insulation thickness | mm | 1.00 |
Pilot Conductor | ||
Number and cross section | mm2 | 1×6 |
Stranding | mm | 84/0,30 |
Conductor diameter | Nom. mm | 3.30 |
Insulation thickness | mm | 1.00 |
Cable details | ||
Min. overall diameter | mm | 24.7 |
Max. overall diameter | mm | 26.7 |
Min. bending radius | mm | 241 |
Radial diameter of outer sheath | mm | 3.0 |
Max. pulling tension | kgf | 218 |
Appx. cable weight | kg/km | 1.15 |
Copper weight | kg/km | 400 |
Electrical details | ||
“Continuous current rating at 25°C Ambient” | A | 46 |
Short curc›it current for 1 s | A | 908 |
Max. DC resistance at 20°C | ||
Phase and earth conductors | Ω /km | 11 |
Pilot Conductor | Ω /km | 11 |
3 screens in parallel connection | Ω /km | 3.48 |