Home » BS Types » BS 6708 TYPE 201

BS 6708 TYPE 201

BS 6708 TYPE 201

Certificates :

APPLICATION

Used for supplying excavating, crushing machines
and equipment.

CONDUCTOR : Electrolytic, stranded, tinned copper wire IEC 60228 Class 5
INSULATION : EPR
SCREEN : Tinned copper / Nylon braided screen over phase cores.
LAYUP : All cores are laid up in contact with each other.
BEDDING : Rubber based bedding compound.
ARMOUR : Galvanized steel pliable armour.
OUTER SHEATH : Heavy duty chloroprene outer sheath

RELATED STANDARDS : BS 6708
RATED VOLTAGE : 640/1100 V
TEST VOLTAGE : 3 kV

Cross Section3×103×163×253×353×503×703×953×120
Conductors
Number and cross sectionmm23×103×163×253×353×503×703×953×120
Strandingmm80/0,40126/0,40196/0,40276/0,40396/0,40360/0,50475/0,50608/0,50
Conductor diameterNom. mm4.405.507.108.4010.1011.9013.9015.50
Insulation thicknessmm1.51.51.61.61.61.82.02.2
Cable details
Radial thickness of inner sheathmm2.52.52.52.52.52.53.83.8
Min. inner sheath diametermm25.528.732.235.239.544.552.556.6
Max. inner sheath diametermm27.530.734.237.241.547.055.559.6
Size of armourmm7/0,717/0,717/0,717/0,717/0,717/0,907/1,257/1,25
outer sheath thicknessmm3.83.84.14.44.95.45.96.3
Min. overall diametermm37.340.644.648.353.660.771.876.7
Max. overall diametermm39.843.447.451.157.464.575.881.0
Min. bending radiusmm398434474511574645758810
Appx. cable weightkg/km2.523.223.854.65.717.4510.2511.8
Copper weightkg/km4887411.011.3681.862.5563.3564.086
Electrical details
“Continuous current
rating at 25°C Ambient”
A6385110135170205250295
Max. DC resistance at 20°C
Phase conductorsΩ /km1.951.240.7950.5650.3930.2770.2100.164
ArmourΩ /km2.01.91.31.21.10.940.800.74
3 screens in parallel connectionΩ /km1.331.611.101.201.400.700.850.50
We use cookies on our website to provide you a better experience. For detailed information please visit our Cookie Policy and Clarification Text.