(N)SSHCÖU

Certificates :

APPLICATIONS

The cables are suitable for fixed installation and flexible operation as motor power supply cables for frequency converter controlled drives in the mining and tunneling

CONDUCTOR: Electrolytic annealed, class 5 stranded tinned copper wires
INSULATION: 3GI3 type cross-linked elastomeric compound (VDE 0207 – Part 20)
SCREEN: Concentric tinned copper wire braiding
INNER SHEATH: GM1b type cross-linked elastomeric compound (VDE 0207 – Part 21)
OUTER SHEATH: 5GM5 type cross-linked elastomeric compound (VDE 0207 – Part 21)
COLOR: Yellow or Black

RATED VOLTAGE: 600 / 1000 V (U0/U)
AC TEST VOLTAGE: 3 kV
OPERATING TEMPETATURE
IN FLEXING USE: -25°C to +80°C
IN FIXED USE: -40°C to +80°C
MAX. CONDUCTOR OPERATING TEMP.: 90°C
CONDUCTOR SHORT-CIRCUIT TEMP.: 250°C (Max. allowable time 5 sec)
MIN. INSTALLATION TEMP.: -15°C
MIN. BENDING RADIUS: VDE 0298-3 Tab.3
CURRENT CARRYING CAPACITIES: VDE 0298-4 Tab. 15

Cross Section (mm²)Nominal Overall Diameter (mm)Approximate Weight
(kg / km)
Min.Bending Radius
(free movement) (mm)
Max. Resistance of Conductors
at 20°C (ohm / km)
2×1,5 12,50 228 63 13,70 
2×2,5 14,30 291 72 8,21 
2×4 17,30 445 87 5,09 
2×6 18,40 519 92 3,39 
2×10 22,20 764 111 1,95 
2×16 24,40 964 122 1,24 
3×35+3×16/3 33,20 2151 166 0,565 
3×50+3×25/3 40,20 3171 201 0,393 
3×70+3×35/3 45,40 4165 227 0,277 
3×95+3×50/3 49,50 5161 248 0,21 
3×120+3×70/3 56,50 6840 283 0,164 
3×150+3×70/3 58,40 7537 292 0,132 
3×185+3×95/3 63,00 8900 315 0,108 
3×240+3×120/3 73,80 11846 369 0,0801 
4×1,5 14,00 298 70 13,70 
4×2,5 17,30 459 87 8,21 
4×4 18,80 572 94 5,09 
4×6 20,10 680 101 3,39 
4×10 24,60 1029 123 1,95 
4×16 28,20 1415 141 1,24